Rack PDU 2G, Metered-by-Outlet, ZeroU, 20A, 208V, (21) C13 & (3) C19

Model: AP8459NA3

  • Input: 200V, 208V, 230V
  • Input Connections: NEMA L6-30P
  • Cord Length: 10 feet (3.05 meters)
  • Output: 200V, 208V
  • Output Connections: IEC 320 C13, IEC 320 C19
Compare
Project List
Product Info
Tech Specs
Documents
APC Metered-by-Outlet Rack PDU, Input: 200V, 208V, 230V, Input Connections: NEMA L6-20P, Cord Length:10 feet ( 3.05 meters ), Output: 208V, Output Connections: IEC 320 C13,IEC 320 C19. Includes: CAN Port Terminator, Installation guide, Rack Mounting brackets, Safety guide, Serial configuration cable
  • Input: 200V, 208V, 230V
  • Input Connections: NEMA L6-30P
  • Cord Length: 10 feet (3.05 meters)
  • Output: 200V, 208V
  • Output Connections: IEC 320 C13, IEC 320 C19
  • Metering-by-outlet capability: Individual outlet level power metering provides a more granular view of the power distributed to equipment within the enclosure. It also provides the ability to analyze component power trends and perform capacity planning.
  • Network Management Capabilities
    • Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.
    • Allows users to access, configure, and manage rack PDUs from remote locations to save valuable time.
    • Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.
  • Alarm Thresholds: Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities.)
  • Local Current Monitoring Display
    • The aggregate current draw per rack PDU is displayed on the unit via a digital display.
    • The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip.
  • Load indicator LED
    • Indicates overload and warning conditions based on the user-defined alarm thresholds.
    • Alerts users of potential overloaded circuits. (Note: Only available with units with local current monitoring feature)
  • Flash Upgradeable: Quickly and easily upgrade firmware via network download for future product enhancements. Eliminates the need to replace products already installed in the field when new features are released (Note: Networked units only).
  • Integrates with StruxureWare Data Center Expert
    • An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
  • Agility features
    • Single input power source: Supply power from one branch whip to multiple pieces of equipment, conveniently powering rack-mount equipment. Saves time and money during installation by using one branch whip and standard connections.